SWITCHlan Trouble Tickets

Transparency is very important to us. We therefore publish all trouble tickets about issues that have an impact on our customers. We show both currently open tickets as well as all closed tickets.

Ticket 20090401_2

Ticket Number: 20090401_2Ticket State: CLOSED
Ticket Opened: 2009-04-01 13:33Ticket Closed: 2009-04-02 11:00
Ticket Description: Site SLF Davos unreachable

Problem Description:

The site SLF in Davos was unreachable on our monitoring tool between 13:25 and 13:35.

A regional power outage in Davos caused the loss of the main power at 13:13 for both power supplies #1 of swiSLF1 and swiSLF2. The routers continued to operate with power supplies #2 powered from the UPS. At 13:25 also the UPS battery capacity was exhausted and both power supplies #2 lost power, causing the ineluctable shutdown of swiSLF1 and swiSLF2.


From 2009-04-01 13:25 until 2009-04-01 13:35
Impact: Total loss of connectivity
Sites/Services: WSL/SLF


2009-04-02 11:00
Routers have been running stable since now. Closing ticket.

2009-04-01 13:35
Router SFL1 and SLF2 are reachable again, after power failure.

2009-04-01 13:30
Nagios alarm ACK